Performance Evaluation of Dynamic Voltage Restorer Under Asymmetrical Faults and Dynamic Unbalanced Loads

Performance Evaluation of Dynamic Voltage Restorer Under Asymmetrical Faults and Dynamic Unbalanced Loads

Raed Najim Ibrahim* | Mohammed Y. Suliman | Mohamed Salem Mohamed Othman

Department of Electrical Engineering Techniques, Engineering Technical College of Mosul, Northern Technical University, Mosul 41001, Iraq

School of Electrical and Electronic Engineering, Universiti Sains Malaysia, Nibong Tebal 14300, Malaysia

Corresponding Author Email: 
raed.nagim@ntu.edu.iq
Page: 
2917-2925
|
DOI: 
https://doi.org/10.18280/jesa.591013
Received: 
30 July 2026
|
Revised: 
16 September 2026
|
Accepted: 
4 October 2026
|
Available online: 
31 October 2026
| Citation

© 2026 The authors. This article is published by IIETA and is licensed under the CC BY 4.0 license (http://creativecommons.org/licenses/by/4.0/).

OPEN ACCESS

Abstract: 

Asymmetrical faults and time-varying phase-voltage disturbances cause voltage unbalance in three-phase distribution systems. This paper evaluates a dynamic voltage restorer (DVR) using conventional discrete direct-quadrature proportional-integral (dq-PI) load-voltage feedback in MATLAB/Simulink. The tests cover single line-to-ground (SLG), line-to-line (LL), and double line-to-ground (LLG) faults, programmed single-phase source-voltage modulation, and unbalanced load switching. Voltage-unbalance factor (VUF) and root-mean-square (RMS) phase-voltage error are assessed in per unit (p.u.). For the LLG fault, phase-A and phase-B RMS values increase from 0.126 and 0.118 to 0.983 and 0.981 p.u. with compensation. In the switched-load test, phase-RMS deviations reach about 12%, consistent with an unregulated zero-sequence component; the cause was not isolated. The low VUF therefore indicates negative-sequence reduction rather than complete restoration of phase magnitudes. The results apply to the investigated simulation model.

Keywords: 

dynamic voltage restorer, voltage unbalance, asymmetrical faults, single-phase voltage modulation, unbalanced load switching, power quality

1. Introduction

Three-phase distribution networks increasingly supply sensitive power-electronic loads, making voltage quality at the load terminals important for reliable operation [1, 2]. Voltage sag and swell are well-known disturbances, while voltage unbalance arises when unequal phase magnitudes or angles introduce negative-sequence components. Unbalance is associated with asymmetrical faults, unequal single-phase loading, feeder-impedance asymmetry, and uneven distributed generation [2, 3], and can produce negative-sequence currents and associated equipment stress.

A dynamic voltage restorer (DVR) is a series compensator that injects a controlled voltage to restore the load voltage [1, 4]. Previous DVR studies have mainly advanced controller design or gain selection. Rahman and Dagnew [5] examined voltage-sag compensation using a direct-converter-based DVR with error-signal modulation. Hassanein et al. [6] applied a DVR in an off-grid hybrid renewable-energy system. Rawa et al. [7] used the gorilla troops algorithm to tune proportional-integral (PI) control; Mahmoud et al. [8] applied Harris hawks optimisation to DVR controllers in a low-voltage smart distribution system; Salman et al. [9] compared particle-swarm optimisation with trial-and-error PI tuning; Setty et al. [10] employed hybrid PI-fuzzy control for sag and swell in a photovoltaic (PV)-based network; and Abdelaal et al. [4] examined sliding-mode DVR control for voltage-sag compensation.

These studies address voltage-sag compensation [5], parameter optimisation in diverse DVR operating conditions [7-9], and hybrid control of sag and swell [10]. By contrast, this work quantifies fundamental negative-sequence reduction using voltage-unbalance factor (VUF) under three asymmetrical faults, programmed single-phase source-voltage modulation, and switched phase-dependent loads, while retaining a conventional discrete direct-quadrature proportional-integral (dq-PI) controller. The experiments report regulation accuracy and its limits, rather than a new controller or a cross-controller benchmark.

Because both DVR voltage compensation and some unbalance cases have been studied previously, this paper does not claim a new control algorithm, transformation, modulation technique, or fault category. The investigated controller uses direct–quadrature (dq) coordinates in a synchronous reference frame (SRF) with load-voltage feedback.

The main contributions of this study are as follows:

1. Quantitative evaluation of a conventional discrete dq-PI-controlled DVR using load-voltage feedback during three asymmetrical faults, programmed single-phase source-voltage modulation, and unbalanced load switching.

2. Consistent assessment of the VUF and mean root-mean-square (RMS) phase-voltage error across the three faults, two source-modulation windows, and a distinct switched-load test.

3. Disclosure of the model, controller gains, fault settings, and two distinct time-varying operating tests.

2. Construction of the Dynamic Voltage Restorer

The DVR connects in series with the load bus and uses a voltage-source inverter (VSI), filter, injection transformer, and direct-current (DC) supply to regulate load voltage [1, 11, 12]. This configuration is shown in Figure 1.

Figure 1. Single-line diagram of the dynamic voltage restorer (DVR) connected in series with the feeder

2.1 Voltage source inverter

The VSI synthesises phase-selective compensating voltages using pulse-width modulation (PWM) [1, 13]. Independent converter-leg switching supports unequal phase-voltage injection [13, 14].

2.2 Injection transformer

The injection transformer transfers the inverter voltage to the feeder and provides galvanic isolation [1, 11, 15]. Its series-voltage capability depends on winding settings, leakage impedance, and saturation margins [16]; the implemented model parameters appear in Section 7.

2.3 Passive filters

An inductor-capacitor (LC) output filter attenuates inverter switching components before series injection [1, 13].

2.4 Energy storage unit

The DC-link supply provides the active energy required for voltage injection [9, 17]. Energy storage or renewable sources may be used [17]; the simulated link is an ideal 200 V DC source and requires a stable voltage for PWM control [1].

2.5 Unbalanced loads

Unequal phase loading, feeder impedance and distributed generation can produce negative-sequence voltage and current components [1, 3]. Their effects include equipment heating and additional losses [1, 2]. The measurements below separate voltage-magnitude error from the negative-sequence VUF [2, 3].

3. Operating Principle of the Dynamic Voltage Restorer

The investigated DVR regulates the measured three-phase load voltage through synchronous-reference-frame feedback. The load-voltage errors drive discrete PI control commands that actuate the PWM inverter, filter, and series injection transformer; the source, injected, and load voltages satisfy Eq. (7) with consistent terminal polarity.

3.1 Operating modes of the dynamic voltage restorer

3.1.1 Standby condition

During nominal supply conditions, the measured load voltage remains close to the balanced reference; the load-voltage errors and series-injection commands are small, and the controller continues to regulate. No bypass switch or protection logic is included in the simulated model; the DVR remains in series operation throughout.

3.1.2 Injection mode

When a disturbance occurs, the measured load-voltage error produces d- and q-axis controller commands. Following the inverse transformations, the PWM inverter, output filter, and series transformer synthesise the compensating voltage in accordance with the series-voltage relationship in Eq. (7).

The documented control path processes load-voltage feedback continuously; it does not establish a separate, threshold-triggered fault detector. Following fault clearance, the controller remains in closed-loop operation while the measured inverter-side voltage decreases; no bypass switch or protection logic is included in the model.

4. Compensation Strategies

The tested compensation strategy regulates the measured load voltage to a 1 p.u. d-axis reference with q-axis reference zero using discrete closed-loop feedback; no separate pre-sag or in-phase look-up strategy is implemented. The required injected voltage depends on disturbance magnitude and phase, and thereby affects DC-link energy and converter rating [2, 9, 18].

5. Conventional Synchronous-Frame Control

The load-voltage signal vabc = [va, vb, vc]ᵀ is measured at BUS 2, the load bus immediately downstream of the series injection stage. The phase-to-ground voltage is expressed in per unit (p.u.) using a nominal line-to-line (LL) RMS voltage VLL = 400 V, corresponding to 326.6 V peak phase-to-ground. The Simulink abc-to-dq0 block provides the Clarke–Park transformation, whose stationary-frame components are defined in Eq. (1):

$\left[\begin{array}{l}v_\alpha \\ v_\beta\end{array}\right]=\frac{2}{3}\left[\begin{array}{ccc}1 & -\frac{1}{2} & -\frac{1}{2} \\ 0 & \frac{\sqrt{3}}{2} & -\frac{\sqrt{3}}{2}\end{array}\right]\left[\begin{array}{l}v_a \\ v_b \\ v_c\end{array}\right]$      (1)

A discrete virtual phase-locked loop (PLL) supplies the electrical angle θ = ωt. With the rotating frame aligned 90° behind the phase-A axis at θ = 0, Eq. (2) converts the stationary-frame voltages into d- and q-axis components. For a balanced positive-sequence nominal voltage under this sine-reference convention, vd = 1 p.u. and vq = 0; the zero-sequence component is not regulated.

$\left[\begin{array}{l}v_d \\ v_q\end{array}\right]=\left[\begin{array}{cc}\sin \theta & -\cos \theta \\ \cos \theta & \sin \theta\end{array}\right]\left[\begin{array}{l}v_\alpha \\ v_\beta\end{array}\right]$          (2)

The controller uses vd,ref = 1 p.u. and vq,ref = 0. The measured components are subtracted from these references to form the two feedback errors:

${{e}_{d}}={{v}_{d,\text{ref}}}-{{v}_{d}},{{e}_{q}}={{v}_{q,\text{ref}}}-{{v}_{q}}$         (3)

The errors are processed by conventional PI controllers. Their outputs ud and uq are modulation commands and not directly measured series-injected voltages:

$\begin{aligned} & u_d(t)=K_{p, d} e_d(t)+K_{i, d} \int_0^t e_d(\tau) d \tau, \\ & u_q(t)=K_{p, q} e_q(t)+K_{i, q} \int_0^t e_q(\tau) d \tau .\end{aligned}$            (4)

The empirical gains are Kp,d = 40, Ki,d = 154, Kp,q = 25, and Ki,q = 260 (Table 1). The inverse Park transformation uses the same PLL angle and the same reference-frame convention:

$\left[\begin{array}{l}u_\alpha \\ u_\beta\end{array}\right]=\left[\begin{array}{cc}\sin \theta & \cos \theta \\ -\cos \theta & \sin \theta\end{array}\right]\left[\begin{array}{l}u_d \\ u_q\end{array}\right]$          (5)

The inverse Clarke transformation with zero commanded zero-sequence component (u₀ = 0) then generates the three-phase commands:

$\left[\begin{array}{l}u_a \\ u_b \\ u_c\end{array}\right]=\left[\begin{array}{cc}1 & 0 \\ -\frac{1}{2} & \frac{\sqrt{3}}{2} \\ -\frac{1}{2} & -\frac{\sqrt{3}}{2}\end{array}\right]\left[\begin{array}{l}u_\alpha \\ u_\beta\end{array}\right], \quad u_0=0$        (6)

Assuming consistent voltage polarity and neglecting intervening series drops, the source, load, and actual injected phase voltages satisfy:

${{\text{v}}_{\text{load},abc}}={{\text{v}}_{\text{source},abc}}+{{\text{v}}_{\text{inj},abc}}$           (7)

The PI outputs ${{u}_{d}}$ and ${{u}_{q}}$ undergo Eqs. (5) and (6), followed by a unity-gain block before the PWM reference. Each unit modulation command corresponds to an ideal inverter fundamental phase voltage of 100 V peak (70.7 V RMS) with the 200 V DC link; the physical series-injected voltage also depends on the filter and transformer.

The three-phase commands enter the synchronised two-level PWM generator without additional reference normalisation. The PWM block operates in synchronised mode at switching ratio 2225 with a 20 µs sample time. At 50 Hz this ratio gives a nominal carrier of 111.25 kHz, exceeding the 50 kHz update rate; the carrier cycle is not temporally resolved, so the reported results concern fundamental load-voltage regulation rather than resolved switching harmonics.

Table 1. System parameters of the investigated dynamic voltage restorer (DVR)-based distribution system

Parameter

Value

AC Source and Network

Grid line voltage (rms, L–L)

11 kV

System frequency

50 Hz

Step-down transformer rating

1 MVA

Transformer voltage ratio

11 kV/400 V

Transformer connection

Dyn (Δ-Yg)

Load-bus (distribution) voltage

400 V

Load

Load configuration

Three-phase, Y-grounded, parallel RLC

Active power, P

1.5 kW

Inductive reactive power, QL

500 var

Capacitive reactive power, QC

0 var

DVR Power Circuit

Converter topology

Three-phase two-level Voltage Source Inverter (VSI) (6 IGBTs)

DC-link voltage, Vdc

200 V

Output filter inductance, Lf

6 mH

Output filter capacitance, Cf

20 μF

Series injection transformer

Three-phase linear, 1.5 kVA, 1:10 (Table 2)

Control, Modulation and Solver

Controller type

SRF-based dq PI controller

PI gains, d-axis (Kp/Ki)

40/154

PI gains, q-axis (Kp/Ki)

25/260

Modulation technique

Sinusoidal PWM (SPWM)

PWM switching ratio (carrier/fundamental)

2225 (dimensionless)

Fixed-step sample time, Ts

2 × 10⁻⁵ s

Simulation environment

MATLAB/Simulink

Note: VSI = voltage-source inverter; IGBT = insulated-gate bipolar transistor; SRF = synchronous reference frame; SPWM = sinusoidal pulse-width modulation; PI = proportional–integral; PLL = phase-locked loop; dq = direct–quadrature; RMS = root-mean-square; p.u. = per unit.

6. Discrete Proportional-Integral Gain Selection

The DVR control scheme is shown in Figure 2. Two conventional discrete proportional–integral controllers regulate the synchronous-frame load-voltage errors according to Eq. (4), using the gains listed in Table 1. The resulting ud and uq commands are transformed to three-phase PWM references through Eqs. (5) and (6).

Figure 2. Control scheme of the investigated conventional dynamic voltage restorer (DVR)

We selected the PI gains by manual iterative tuning in MATLAB/Simulink: Kp,d = 40, Ki,d = 154, Kp,q = 25, and Ki,q = 260 (Table 1). The d- and q-axis gains were tuned separately, and no analytical justification for the difference between them is claimed. Both discrete PI blocks use a 20 µs sample time and forward-Euler integration, zero initial output, and output limits of ±1.1 relative to a PWM carrier range of ±1. These limits permit mild over-modulation under severe disturbances. No separate anti-windup scheme is claimed. Poles, gain and phase margins, and settling time were not computed; no analytical stability proof is claimed.

7. Investigated System Model

Design check. Figure 3 shows an 11/0.4 kV feeder with a 1 MVA upstream transformer and a 1.5 kW/500 var test load, with an apparent power of approximately 1.581 kVA (0.158% of the transformer rating). The DVR is supplied by an ideal 200 V DC source and uses a linear series injection transformer with nominal model settings of 10 V and 100 V RMS (1:10) and 1.5 kVA.

Figure 3. MATLAB/Simulink model of the investigated dynamic voltage restorer (DVR)-based distribution system

During the LLG fault, the inverter-side RMS phase voltages over 0.10-0.20 s were 23.2390, 21.5291 and 1.5360 V, corresponding through the 1:10 ratio to approximately 232, 215 and 15 V on the series side (an ideal-ratio estimate, not a direct measurement). The first two exceed the nominal model settings. For an ideal two-level inverter with sinusoidal PWM at unity modulation index, the 200 V DC link gives a theoretical fundamental phase-voltage limit of approximately 70.7 V RMS. The transformer is modelled as linear with specified winding resistance, leakage and magnetising parameters, but without saturation, thermal or winding-current limits; the results therefore describe the simulation model and do not establish that the listed settings are adequate for a physical implementation.

Figure 3 shows the 200 V DC source, two-level VSI, output filter and series injection transformer. The BUS 2 load-voltage measurement supplies the conventional discrete dq–PI feedback loop described in Sections 5 and 6; the transformer model settings are listed in Table 2.

Table 2. Model settings of the dynamic voltage restorer (DVR) series injection transformer used in the simulation

Parameter

Value

Configuration

Three-phase linear transformer (12-terminal), series

Nominal power (model setting)

1.5 kVA

Nominal frequency (model setting)

50 Hz

Primary voltage (V1, RMS; nominal model setting)

10 V

Secondary voltage (V2, RMS; nominal model setting)

100 V

Turns ratio (N1:N2)

1:10

Primary resistance, R1

1 × 10⁻⁵ pu

Primary leakage reactance, X1

3 × 10⁻⁴ pu

Secondary resistance, R2

1 × 10⁻⁵ pu

Secondary leakage reactance, X2

3 × 10⁻⁴ pu

Magnetizing resistance, Rm

200 pu

Magnetizing reactance, Xm

200 pu

Note: p.u. means per unit; RMS means root-mean-square. All winding voltages and apparent power are nominal model settings, not verified hardware ratings.

The BUS 2 load-voltage feedback uses the PLL, synchronous-frame transformations, and discrete PI controllers of Sections 5 and 6. Section 8.4 documents the source-modulation and switched-load configurations separately.

8. Results and Discussion

The results are interpreted through the conventional feedback structure and fixed controller gains (Sections 5 and 6): the asymmetrical fault cases appear in Sections 8.1-8.3, the source-voltage and switched-load tests in Section 8.4, and the measured controller response and regulation limits in Section 8.5. All three asymmetrical faults started at 0.05 s and were cleared at 0.25 s (duration 0.20 s), with fault resistance 0.003 Ω. They comprised a single line-to-ground (SLG) fault on phase A, an LL fault on phases A and B, and a double LLG fault on phases A and B and ground. Grounding resistance was 0.001 Ω for SLG and LLG and did not apply to the ungrounded LL fault. Source-side RMS voltages were evaluated over 0.10–0.20 s relative to the nominal 1 p.u. base; the corresponding voltage drops were 86.5% (phase A, SLG), 41.8% and 58.2% (phases A and B, LL), and 87.4%, 88.2%, and 6.4% (phases A, B, and C, LLG).

Voltage unbalance was quantified using the VUF computed from the fundamental positive- and negative-sequence phase-voltage phasors:

$\mathrm{VUF}=\frac{\left|V_2\right|}{\left|V_1\right|} \times 100 \%$     (8)

where, $V_1=\left(V_a+a V_\beta+a^2 V_c\right) / 3$ and $V_2=\left(V_{\mathrm{a}}+a^2 V_\beta+a V_c\right) / 3$, where $\mathrm{a}=\exp (\mathrm{j} 2 \pi / 3)$. "Before" values are taken from BUS 1 in the same simulation run; "after" values are measured at BUS 2 downstream of series injection.

8.1 Single line-to-ground fault

The SLG fault reduces one phase while the other two remain unchanged, creating supply-side voltage unbalance. Figure 4(a) shows the uncompensated condition, in which the load voltage follows the disturbed supply and remains unbalanced. In Figure 4(b), the DVR injects voltage only into the disturbed phase during the fault interval; the healthy phases remain unaffected, and the disturbed phase is restored toward the healthy-phase magnitude. Over 0.10–0.20 s, Table 3 reports a source-side VUF of 53.1844%, compared with 0.4426% at the compensated load; the mean post-compensation RMS voltage error was 0.8983%.

Table 3. Voltage-unbalance factor (VUF) and root-mean-square (RMS) voltage errors for single line-to-ground (SLG), line-to-line (LL), and double line-to-ground (LLG) faults and programmed single-phase source-voltage modulation with a dynamic voltage restorer (DVR)

Operating Condition

VUF Before (%)

VUF after (%)

Mean Voltage Error after (%)

SLG fault

53.1844

0.4426

0.8983

LL fault

97.3796

0.5919

0.9921

LLG fault

93.3615

0.3866

1.2517

Source modulation – rise

14.0818

0.1473

0.1541

Source modulation – drop

19.5932

0.1674

0.1522

Note: "Before" denotes source-side phase voltages measured at BUS 1 in the same simulation run; "after" denotes load-side voltages measured at BUS 2. VUF uses the 50 Hz fundamental positive- and negative-sequence phasors. Mean voltage error after compensation is the average absolute departure of the three-phase root-mean-square (RMS) values from 1 per unit (p.u.). The evaluation window is 0.10–0.20 s for faults, 0.40–0.50 s for the source-modulation rise, and 0.90–1.00 s for the drop. Voltages are logged on a 326.6 V peak phase-to-ground base: RMS in p.u. equals √2 times the RMS of the plotted per-unit waveform (1 p.u. RMS equals 230.9 V RMS phase-to-ground).

Figure 4. Voltage waveforms during a single line-to-ground (SLG) fault: (a) without dynamic voltage restorer (DVR) compensation; (b) with DVR compensation

8.2 Line-to-line fault

The LL fault disturbs two phases, producing an asymmetric load-side voltage when no compensation is applied. Figure 5(a) shows the reduction of the two affected phases and the resulting load-side unbalance. Figure 5(b) shows the DVR injecting the required series voltage into the two disturbed phases during the fault interval, restoring the load voltage toward a balanced three-phase waveform. Table 3 gives a source-side VUF of 97.3796% and a compensated load-side value of 0.5919%; the mean post-compensation RMS voltage error was 0.9921%.

Figure 5. Voltage waveforms during a line-to-line (LL) fault: (a) without dynamic voltage restorer (DVR) compensation; (b) with DVR compensation

8.3 Double line-to-ground fault

The LLG fault strongly depresses phases A and B, while phase C is less affected. Figure 6(a) shows the uncompensated condition, with the load voltage following the severe two-phase depression. Figure 6(b) shows DVR compensation during the fault. Over 0.10–0.20 s, phase-A and phase-B RMS voltages improve from 0.126 and 0.118 to 0.983 and 0.981 p.u., respectively, while phase C reaches 1.002 p.u. Table 3 reports a reduction in the VUF from 93.3615% to 0.3866%, with a mean post-compensation RMS voltage error of 1.2517%. The "Vinj" trace in Figure 6(b), approximately 0.1 p.u. peak, is measured on the inverter side of the 1:10 transformer; it is not a direct measurement of the line-side injected voltage.

Figure 6. Voltage waveforms during a double line-to-ground (LLG) fault: (a) without dynamic voltage restorer (DVR) compensation; (b) with DVR compensation
Note: The Vinj subplot displays inverter-side phase-to-ground voltage (p.u. on the 326.6 V peak phase-to-ground base, equivalent to 400 V line-to-line RMS), not the physical line-side series-injected voltage. Here, p.u. denotes per unit and RMS denotes root-mean-square.

8.4 Time-varying source and switched-load tests

Figure 7(a) shows the uncompensated response to programmed single-phase source-voltage modulation, while Figure 7(b) identifies the source-side phase voltages at the 11 kV bus and at BUS 1, each on its own per-unit base. The programmed 11 kV, 50 Hz source is connected to phase A through a breaker, with phases B and C not modulated. During 0.2–1.2 s, the phase-A amplitude follows 11 kV × [1 + 0.5 sin(2π × 1 × (t − 0.2))]. It reaches about 1.5 p.u. near 0.45 s and about 0.5 p.u. near 0.95 s; Figure 7(c) shows DVR compensation.

(a)

(b)

(c)

Figure 7. Voltages under programmed single-phase source-voltage modulation: (a) without the dynamic voltage restorer (DVR); (b) source-side phase voltages at the 11 kV bus and at BUS 1, each in per unit (p.u.) on its respective voltage base; (c) with DVR compensation

During the source-modulation rise (0.40-0.50 s) and drop (0.90-1.00 s), source-side VUFs were 14.0818% and 19.5932%, while the compensated BUS 2 values were 0.1473% and 0.1674%, respectively (Table 3). The corresponding mean phase RMS voltage errors after compensation were 0.1541% and 0.1522%. The residual fluctuation in Figure 7(c) is part of the expected closed-loop response: the PI loop has finite bandwidth, and the disturbance is a continuously varying 1 Hz amplitude modulation, so the load voltage follows it with a small residual error. The compensated mean RMS errors of 0.1541% and 0.1522% in the rise and drop windows bound this residual. The three-phase dynamic-load block is a balanced positive-sequence representation and does not produce this single-phase source disturbance.

For the separate switched-load test, the grounded-wye base load had phase active powers of 600/500/400 W (A/B/C) and inductive reactive powers of 200/170/130 var. A parallel phase-dependent load of 150/100/50 W and 50/30/20 var was connected at 0.35 s and disconnected at 0.85 s; capacitive power was zero. Nominal phase-power unbalance, defined as the maximum absolute departure from the three-phase mean divided by the mean, changed from 20%/22% to 25%/25% (active/reactive) and then returned to 20%/22%. Table 4 reports the corresponding measured load-voltage performance. During the connected interval, a low negative-sequence VUF coexisted with phase RMS deviations up to 12.4%; the measured 50 Hz zero-sequence magnitude was 14.1212% of the positive sequence, and the dq controller did not independently regulate the zero sequence. These observations do not establish a unique cause of the phase-voltage spread. No DVR-disabled benchmark was evaluated for this switched-load test, and complete phase-voltage restoration is not claimed.

Table 4. Switched-load phase-power unbalance and compensated load-voltage performance

Window (s)

P/Q Unbalance (%)

VUF after (%)

Mean RMS Error (%)

Phase RMS A/B/C (p.u.)

0.25–0.33

20/22

0.2067

6.4417

0.9032/0.9985/1.0949

0.40–0.50

25/25

0.4076

8.4020

0.8758/1.0037/1.1241

0.90–1.00

20/22

0.2255

6.5448

0.9079/1.0035/1.1008

Note: P and Q denote active and inductive reactive phase powers, respectively; unbalance is the maximum absolute departure from the phase mean divided by that mean. VUF = voltage-unbalance factor; RMS = root-mean-square; p.u. = per unit. Values are compensated load-side measurements, not a dynamic voltage restorer (DVR)-disabled comparison.

8.5 Controller response and regulation limits

The investigated DVR uses the conventional discrete dq–PI controller described in Sections 5 and 6; this study evaluates its performance under the specified fault, source-modulation and switched-load conditions rather than proposing a new control method. Table 3 compares source-side and compensated load-side VUFs, and reports mean compensated RMS errors. A separate controller-to-controller reference comparison was not simulated, so comparative superiority is not claimed.

To quantify the dynamic response, we evaluated the exported inverter-side phase-to-ground voltage (Vinj), measured before the series injection transformer, using a trailing 1 ms RMS window, a 0.01 p.u. threshold, and a 2 ms persistence condition. After fault initiation at 0.05000 s, the first sustained above-threshold instants in the affected phases were 0.05008 s for SLG (phase A), 0.05006 s for LL (phases A and B), and 0.05004 s for LLG phase B (0.05008 s for phase A). After fault clearance at 0.25000 s, all affected inverter-side phases remained below this threshold from 0.25378 s (SLG), 0.25222 s (LL), and 0.26036 s (LLG). These post-processed threshold crossings characterise inverter-side voltage activity, not a separate fault-detection latency or direct measurements of physical line-side injection.

Load-voltage recovery was assessed separately using trailing one-cycle RMS magnitudes (20 ms at 50 Hz), with an acceptance band of 0.95-1.05 p.u. for all three load phases and a one-cycle persistence requirement. For SLG, LL, and LLG, the computed load-phase RMS values remained within this band throughout 0.07–0.25 s. Because the moving RMS window averages the voltage across the disturbance onset, and no distinct out-of-band-to-in-band transition was resolved, a numerical load-voltage recovery or settling time cannot be established from this criterion; none is claimed.

The measured load-side VUFs during SLG, LL, and LLG faults were 0.4426%, 0.5919%, and 0.3866%, respectively, with mean phase RMS voltage errors of 0.8983%, 0.9921%, and 1.2517% (Table 3). Under the programmed single-phase source-voltage modulation, the two evaluation windows gave load-side VUFs of 0.1473% and 0.1674%, with mean errors of 0.1541% and 0.1522%, respectively. These existing measurements and the inverter-side threshold observations above document regulation under the simulated operating conditions. The switched-load test had a larger mean RMS error of 8.4020% during load connection (Table 4). Consequently, the fault and source-modulation error bounds cannot be generalised to all unbalanced-load conditions. The results do not provide a small-signal stability proof, gain or phase margins, or a measured 2% settling time. Related zero-sequence DVR approaches are reported [19, 20].

9. Conclusions

This study evaluated the conventional discrete dq-PI-controlled DVR under three asymmetrical faults, programmed single-phase source-voltage modulation, and unbalanced load switching. The voltage unbalance factor decreased from 53.1844% to 0.4426%, from 97.3796% to 0.5919%, and from 93.3615% to 0.3866% in the fault cases. During the two programmed source-modulation windows, it decreased from 14.0818% to 0.1473% and from 19.5932% to 0.1674%; corresponding post-compensation mean RMS errors over all five intervals were 0.8983%, 0.9921%, 1.2517%, 0.1541%, and 0.1522%. These metrics document fundamental negative-sequence regulation but not comparative superiority, analytic stability margins or hardware validation. In the switched-load test, the connected-load mean RMS error was 8.4020%, and the phase-magnitude error reached about 12%, consistent with an unregulated zero-sequence component; the cause was not isolated. The transformer model is linear and does not saturate; the fault cases exceed its nominal winding settings, requiring further hardware-oriented verification. The synchronised PWM ratio exceeds the discrete update resolution and does not support a switching-harmonic claim.

Nomenclature

ed, eq

d- and q-axis load-voltage errors (p.u.)

Kp,d, Kp,q

proportional gains of the two PI controllers

Ki,d, Ki,q

integral gains of the two PI controllers

t

time (s)

ua, ub, uc

three-phase inverter modulation commands

ud, uq

d- and q-axis PI output commands

uα, uβ

stationary-frame commands

va, vb, vc

measured phase-to-ground load voltages (p.u.)

vd, vq

d- and q-axis measured load voltages (p.u.)

vinj,abc

physical series-injected three-phase voltage (V)

vload,abc

three-phase load voltage (V)

vsource,abc

three-phase source voltage (V)

vα, vβ

stationary-frame measured voltage components (p.u.)

VLL

nominal line-to-line rms voltage (V)

θ

PLL electrical angle (rad)

  References

[1] Moghassemi, A., Padmanaban, S. (2020). Dynamic voltage restorer (DVR): A comprehensive review of topologies, power converters, control methods, and modified configurations. Energies, 13(16): 4152. https://doi.org/10.3390/en13164152

[2] Soomro, A.H., Larik, A.S., Mahar, M.A., Sahito, A.A., Soomro, A.M., Kaloi, G.S. (2021). Dynamic voltage restorer—A comprehensive review. Energy Reports, 7: 6786-6805. https://doi.org/10.1016/j.egyr.2021.09.004

[3] Ibrahim, W.Kh., Alkhayyat, M.T., Suliman, M.Y. (2025). Unbalanced voltage enhancement based on STATCOM for distribution network integrated with renewable energy. International Journal of Electrical and Electronics Research, 13(3): 572-579. https://doi.org/10.37391/ijeer.130322

[4] Abdelaal, A.K., Shaheen, A.M., El-Fergany, A.A., Alqahtani, M.H. (2024). Sliding mode control based dynamic voltage restorer for voltage sag compensation. Results in Engineering, 24: 102936. https://doi.org/10.1016/j.rineng.2024.102936

[5] Rahman, S.A., Dagnew, E. (2020). Voltage sag compensation using direct converter-based DVR by modulating the error signal. Indonesian Journal of Electrical Engineering and Computer Science, 19(2): 608-616. https://doi.org/10.11591/ijeecs.v19.i2.pp608-616

[6] Hassanein, W.S., Ahmed, M.M., abed el-Raouf, M.O., Ashmawy, M.G., Mosaad, M.I. (2020). Performance improvement of off-grid hybrid renewable energy system using dynamic voltage restorer. Alexandria Engineering Journal, 59(3): 1567-1581. https://doi.org/10.1016/j.aej.2020.03.037

[7] Rawa, M., Mohamed, H.N., Al-Turki, Y., Sedraoui, K., Ibrahim, A.M. (2023). Dynamic voltage restorer under different grid operating conditions for power quality enhancement with the deployment of a PI controller using gorilla troops algorithm. Ain Shams Engineering Journal, 14: 102172. https://doi.org/10.1016/j.asej.2023.102172

[8] Mahmoud, M.M., Esmail, Y.M., Atia, B.S., et al. (2022). Voltage quality enhancement of low-voltage smart distribution system using robust and optimized DVR controllers: Application of the Harris Hawks Algorithm. International Transactions on Electrical Energy Systems, 2022: 4242996. https://doi.org/10.1155/2022/4242996

[9] Salman, S.S., Humod, A.T., Hasan, F.A. (2022). Optimum control for dynamic voltage restorer based on particle swarm optimization algorithm. Indonesian Journal of Electrical Engineering and Computer Science, 26(3): 1351-1359. https://doi.org/10.11591/ijeecs.v26.i3.pp1351-1359

[10] Setty, S.N., Shashikala, M.S.D., Veeramanju, K.T. (2023). Hybrid control mechanism-based DVR for mitigation of voltage sag and swell in solar PV-based IEEE 33 bus system. International Journal of Power Electronics and Drive Systems, 14(1): 209-221. https://doi.org/10.11591/ijpeds.v14.i1.pp209-221

[11] Danalakshmi, D., Bugata, S., Kohila, J. (2019). A control strategy on power quality improvement in consumer side using custom power device. Indonesian Journal of Electrical Engineering and Computer Science, 15(1): 80-87. https://doi.org/10.11591/ijeecs.v15.i1.pp80-87

[12] Mohammed, A.B., Ariff, M.A.M., Ramli, S.N. (2020). Power quality improvement using dynamic voltage restorer in electrical distribution system: An overview. Indonesian Journal of Electrical Engineering and Computer Science, 17(1): 86-93. https://doi.org/10.11591/ijeecs.v17.i1.pp86-93

[13] Mohammed, J.A.K., Hussein, A.A., Al-Sakini, S.R. (2020). Voltage disturbance mitigation in Iraq's low voltage distribution system. Indonesian Journal of Electrical Engineering and Computer Science, 17(1): 47-60. https://doi.org/10.11591/ijeecs.v17.i1.pp47-60

[14] Deshpande, Chinmay V., Deshpande, Chaitanya V. (2019). Optimum design of dynamic voltage restorer for voltage sag mitigation in distribution network. International Journal of Power Electronics and Drive Systems, 10(3): 1364-1372. https://doi.org/10.11591/ijpeds.v10.i3.pp1364-1372

[15] Tan, K.H., Chen, J.H., Lee, Y.D. (2023). Intelligent controlled dynamic voltage restorer for improving transient voltage quality. IEEE Access, 11: 74686-74699. https://doi.org/10.1109/ACCESS.2023.3293823

[16] Alkhayyat, M.T., Aiwa, F., Alhfidh, A.S., Suliman, M.Y. (2024). Power transformer inrush current minimisation during energization using ANFIS-based peak voltage tracking approach. International Journal of Electrical and Electronics Research, 12(1): 211-218. https://doi.org/10.37391/IJEER.120130

[17] Balasubramani, S., Akshaya, S., Karthick Balaji, A., Harirajan, S., Ramesh Babu, M. (2016). Mitigation of voltage sag using dynamic voltage restorer with super capacitor. International Journal of Advanced Research in Management, Architecture, Technology and Engineering, 2: 425-427. https://doi.org/10.20256/IJARMATE.2016.02030084.

[18] Nielsen, J.G., Newman, M., Nielsen, H., Blaabjerg, F. (2004). Control and testing of a dynamic voltage restorer (DVR) at medium voltage level. IEEE Transactions on Power Electronics, 19(3): 806-813. https://doi.org/10.1109/TPEL.2004.826504

[19] Neto, R., Landera, Y., Neves, F., de Souza, H., Cavalcanti, M., Azevedo, G. (2021). Attenuation of zero sequence voltage using a conventional three-wire dynamic voltage restorer. Energies, 14(5): 1247. https://doi.org/10.3390/en14051247

[20] Liu, D., Zhang, H., Liang, X., Deng, S. (2024). Model predictive control for three-phase, four-leg dynamic voltage restorer. Energies, 17(22): 5622. https://doi.org/10.3390/en17225622